F3200 Installation & Programming Manual

Document No: LT0122

Applications

Page 9-14

5 July 2001

Issue 2.7

AVI SIGNS (CONTINUED)

Function Input

Lamps

Tone

Mode DIL SW

On

DIL Sw

Off

Lk1,2

Lk3

Lk6

Notes

1

Alert-

Both

Top

Both

Alert

Evac

3-wire

std

1,3,5,6 2,4,7,8

1-2

1-2

On

2

Alert-

Both

Top

Both

Alert

Evac

3-wire

std

1,3,5,6 2,4,7,8

1-2

1-2

On

3

Evac-

Both

Evac 2-wire 2,3,5,6 1,4,7,8

2-3

1.2

Off

b.

4

Alert-

Both

None 3-wire

spcl

1,3,5,6,

8

2,4,7

1-2

2-3

On

Notes
a.

The option of top lamps with Evac tone for one input, and both lamps with Evac tone
for the other, is not directly supported. But it can be arranged by mounting the AVI
upside down.

b.

For this configuration the +ve supply is wired into Alert-, not +24V.

FIG 9.2.3

CONNECTION OF MULTIPLE LGCSs

9.2.6 DRAWINGS

The following drawings are included:

1931-47 1 Zone Gas Flood Door, Circuit Diagram
1937-2 Local Gas Control Station, Circuit Diagram