Appendix a2 programming for detector type – Tyco F3200 User Manual

Page 262

Advertising
background image

F3200 Installation & Programming Manual

Document No: LT0122

Appendix A

Page A-6

5 July 2001

Issue 2.7

APPENDIX A2

PROGRAMMING FOR DETECTOR TYPE

1.

GENERAL

The default programming (i.e. pre-programmed options) for AZCs (circuits) and zones are

shown on the top of the "F3200 INPUT CONFIGURATION" sheet in Appendix B. They are

as follows:

Circuits

┌──────────┬────────────┬───────────┬─────────────────┬───────────────┐
│ Alarm │ Mode

│ Delay

│ Voltage Band │ Voltage Band │

│ Text │ │ (Type) │ B1 (0-3V)

│ B3 (13-17.5V) │

├──────────┼────────────┼───────────┼─────────────────┼───────────────┤
│ 1 Smoke │ 1 Standard │1 Standard │ 1 Instant Alarm │1 Instant Alarm│
└──────────┴────────────┴───────────┴─────────────────┴───────────────┘

Zones

┌──────────┬───────────┬───────────┬───────────┬───────────┬───────────┐
│Latch/ │Mapped/Not │Mapped/Not │Mapped/Not │Mapped/Not │LED Map │
│Non-Latch │to MAF │to Anc1 │To Anc2 │To Bells │(Zone n) │
├──────────┼───────────┼───────────┼───────────┼───────────┼───────────┤
│Latch │Mapped │Mapped │Mapped │Mapped │LED n │
└──────────┴───────────┴───────────┴───────────┴───────────┴───────────┘

The default "circuit" programming suits most of the common "electronic" (as opposed to

"hard contact") smoke detectors and hard contact detectors in electronic bases, where these

are not used with external (remote) LED indicators.

Where other types of detector are used, or detectors are used to switch remote LED

indicators directly so that the alarm voltage is out of the B2 range (approx. 3V-13V), the

circuit will have to be programmed accordingly. In some cases constraints are also applied

to zone programming. For example, where a non-latching detector (e.g. Olsen P76B) is

used for air duct sampling, then as well as programming the circuit for the appropriate RAD

or SAD time delay sequence, the zone should be programmed as non-latching.

Programming circuits and zones is described in Sections 7.2 and 7.3 of this manual. The

following describes the relationships between detector types and circuit programming.

2.

ALARM TEXT

Choose the appropriate text for each detector type e.g. smoke (default) for smoke detectors,

heat for thermal detectors, etc. There is provision for creating new names if the standard

ones are not sufficient.

The Instant Alarm text may also be changed if required (default is manual).

3.

MODE

Mode 1 (standard) suits most detectors where remote LEDs are not used.

High Current Detectors

The following detectors require the F3200 circuit to be programmed into high current mode

(mode 2) to give sufficient LED (lamp) illumination current.

Advertising