F3200 Installation & Programming Manual

Document No: LT0122

Installation & Wiring

Page 8-20

5 July 2001

Issue 2.7

8.6

MODULE RELAY WIRING

The 8 Relay Module relays each have one set of voltage free change-over contacts (ie one

pole) accessible via screw terminals, to switch plant equipment. The second pole of each

relay can be accessed by fitting a 3-way de-mountable connector block pair CN0488 and

CN0206.

There are two sets of four inter-connected, voltage free, looping terminals per module that

can be used for looping supplies onto relays or loads.

If the load switched is inductive e.g. a solenoid coil, a suppression diode must be fitted as

shown in Fig 8.6.1.

Supervision

Supervision of the field wiring from the FIP to the load is shown in Fig 8.6.1. This only works

for a single load, or multiple co-located loads wired in parallel (though for multiple co-located

loads, the supervision will not detect a fault if one load becomes disconnected). It requires

the load or an EOLR to be connected between the relay COM terminal and the FIP 0V, and

the supervision link on the module to be fitted in the "S" position. If the COM output does not

‘see’ a supply voltage or open circuit when the relay is activated, then the relay must be

programmed to not supervise the load when actived (requires V2.09 or greater software).

An example of supervising a circuit of multiple, separately located loads using 2 poles of one

relay is shown in Fig 8.5.3.

+VBF o

─────┐

┌─ │

| NO o

─────┘

|
RLn | NC o INDUCTIVE LOAD
| (SEE NOTE)
| COM o

───────────────────────────────────────────┬───────────┐

└─ ┌─┴─┐ ╒╧╕

S

│ │ │ │

───o o └─┬─┘ └┬┘

0V o

───────────────────────────────────────────┴───────────┘

SUPPRESSION

a

. DIODE

Note: For a load of less than 400 Ohms a diode of suitable current rating must be wired in

series with the load at the load as shown in b. below.

──────┬───┐ ──────┐

INDUCTIVE

┌─┴─┐╒╧╕ ┌┴┐

LOAD

│ ││ │DIODE │ │DIODE

└─┬─┘└┬┘ ╘╤╛

├───┘

OR

├───┐

┌┴┐ INDUCTIVE┌─┴─┐╒╧╕

│ │DIODE LOAD│ ││ │DIODE

╘╤╛ └─┬─┘└┬┘

0V

──────┘

0V

─────┴───┘

b.

FIG 8.6.1

EXAMPLES OF MODULE RELAY WIRING WITH SUPERVISION

Advertising