Document No: LT0122

F3200 Installation & Programming Manual

System Specifications

Issue 2.7

5 July 2001

Page 3-5

STATE

MIN

NOM

MAX

COMMENTS

Charger High

28.05

28.125

28.20 Adjust with pot

Charger Low

26.40

26.57

26.75

Battery Low

24.15

24.33

24.55

Standby Off

21.5

22.0

22.5 For voltage falling

Notes:

1. All voltages stated in VDC at temperature of 20

°

C.

2. Apply temperature compensation of -36 mV/

°

C for temperature deviation from 20

°

C.

3. This applies also to charger voltage 27.3 VDC.

4. There are thermal delays, therefore if checking or adjusting in field ensure unit has been

running for some hours.

5. Standby Relay is normally energised (on), and turns off for Battery fail.

TABLE 3.3.2

BATTERY AND CHARGER MONITORING VOLTAGE SPECIFICATIONS

3.3.3 BATTERY

Battery Voltage

:

24Vdc nominal (2 x 12Vdc)

Compatible Makes

Sonnenschein A200 & Sonnenschein A300 series

Powersonic PS12 series

Yuasa NP series

Capacity

:

6 to 50 Ahr

(dependent on configuration)

Space (mm)

:

- Standard Cabinet

Up to 220H, 440W, 175D (Iss B cabinet)

- Small Cabinet

Up to 200H, 185W, 175D (3 modules fitted)

Up to 200H, 370W, 125D (4 modules fitted)

(Refer to Fig 2.2.2)

Battery Test Load

:

46 Ohm nominal. Suitable for 6 Ahr battery (with quiescent

current)

Provision for fitting extra resistors

NOTE:

BATTERY TEST RESISTORS (R52, R53) MUST BE REMOVED FOR NEW
ZEALAND OPERATION.

3.3.4 FUSES

Location

:

MAF/PSU PCB

Number

Name

Size

Rating

Type

F1

+VBF1

5 x 20mm

2A

Glass Cartridge, Std

F2

+VBF2

5 x 20mm

6A

Glass Cartridge, Std

F3

+VNBF

5 x 20mm

2A

Glass Cartridge, Std

F4

+VE

5 x 20mm

2A

Glass Cartridge, Std

F5

Mains In

5 x 20mm

6A

Glass Cartridge, Std

F7

+VBELLS

5 x 20mm

2A

Glass Cartridge, Std