Tyco F3200 User Manual

Page 199

Advertising
background image

Document No: LT0122

F3200 Installation & Programming Manual

Applications

Issue 2.7

5 July 2001

Page 9-29

4 TERMINAL ISOLATED REPEATER WITH ZONE ADAPTOR UNIT ZAU401 (REV 2)
(CONTINUED)

GAS GROUP 11A OR 11B

GAS GROUP 11C

DETECTOR

CCT LENGTH

CCT LENGTH

TYPE

PART

BASE

QTY

1.0mm²

0.75mm²

QTY

1.00mm²

0.75mm²

SMOKE

C29BEx

Z94C

40(M)

3km(R)

2.2km(R)

40(M)

0.9km(C)

0.9km(C)

(100Ω)

(100Ω)

(90nF)

(90nF)

33

0.97km(C)

0.97km(C)

(97nF)

(97nF)

20

1.1km(C)

1.1km(C)

(110nF)

(110nF)

1

1.3km(C)

1.3km(C)

(130nF)

(130nF)

FLAME

R24BEx

-

2(M)

0.5km(R)

.37km(R)

2(M)

0.5km(C)

0.37km(R)

(17Ω)

(17Ω)

(17Ω)

(17Ω )

HEAT

FW105

-

-

-

-

-

1.3km TOT

1.3km TOT

(100Ω TOT)

(100Ω TOT)

(130nF)

(130nF)

40(M)

3km(R)

2.2km(R)

40(M)

1.3km(C)

1.3km(C)

HEAT

T54B

-

(100Ω)

(100Ω)

(130nF)

(130nF)

HEAT

T56B

Z500N

40(M)

3km(R)

2.2km(R)

40(M)

1.13km(C)

1.3km(C)

(100Ω)

(100Ω)

(130nF)

(130nF)

HEAT

S231i+

-

4(M)

3KM (R)

2.2KM (R)

4(M)

1.24KM(C)

1.24KM(C)

(100Ω)

(100Ω)

(124nF)

(124nF)

1

1.28km(C)

1.28km(C)

(128nF)

(128nF)

FLAME

S121

-

16(M)

3km(R)

2.2km(R)

16(M)

0.66km(C)

0.66km(C)

(100Ω)

(100Ω)

(66nF)

(66nF)

10

0.9km(C)

0.9km(C)

(90nF)

(90nF)

1

126km(C)

1.26km(C)

(126nF)

(126nF)

FLAME

MS302Ex

M300

16(M)

3km(R)

2.2km(R)

16(M)

1.06km(C)

1.06km(C)

(100Ω)

(100Ω)

(106nF)

(106nF)

10

1.15km(C)

1.15km(C)

(115nF)

(115nF)

1

1.28km(C)

1.28km(C)

(128nF)

(128nF)

ION

MF301Ex

M300

16(M)

(SAME AS MS302Ex)

PHOTO

MR301Ex

M300

16(M)

(SAME AS MS302Ex)

HPO

MR301TEx

M300

16(M)

(SAME AS MS302Ex)

TABLE 9.4.4

MAXIMUM DETECTOR QUANTITY & CABLE LENGTH FOR

ZAU401 (REV 2) & 4-TERMINAL REPEATER

Notes

1.

Circuit lengths quoted are total from the FIP to the EOL. The length quoted is the

maximum for the corresponding quantity of detectors.

2.

Cable resistance shown is for the circuit, ie. both cables in the pair. The value of 34Ω

per km (return) is used for 1 mm².

3.

The maximum resistances shown for the fire wire circuits must include both cable

and fire wire (see Table 9.4.2 and associated note 2).

4.

The letter in ( ) after the cable length, and the value in ( ) under the cable length

specify which parameter out of capacitance (C), inductance (L) and resistance (R)

provides the limitation, and what the maximum value is.

5.

The (M) after a detector quantity indicates the maximum quantity allowed per circuit.

6.

The maximum allowable detector quantity corresponds to a quiescent current of

1.8mA for C29BEx, 0.3mA for R24BEx.