Tyco F3200 User Manual

Page 127

Advertising
background image

Document No: LT0122

F3200 Installation & Programming Manual

Programming System Configuration

Issue 2.7

5 July 2001

Page 7-25

ENTERING EQUATIONS (CONTINUED)

3.

When an equation has been entered, check it, and count the number of "(" and the

number of ")" to ensure they are the same.

4.

It is recommended that all equations be written on forms (such as in Appendix B)

before they are entered, and then checked against the forms after they have been

entered).

Example

Enter an equation to program module relay 5 to activate if Zones 9 or 10 go into alarm, but

not if Open Collector 4 is active (say open collector 4 drives a status LED and has a logic

equation entered to do this).

The equation is:

R5 = (Z9A + Z10A).^OC4

From the "System Configuration" menu (4), select "Output Logic" (4) followed by "relay" (1).

Use "NEXT" to step onto Relay 5 (R5)

Press

LCD Shows

"""

R5 = $

(NOT AR RL VL █N TM OC ZR NA NV

"("

R5 = ( $

(NOT AR RL VL █N TM OC ZR NA NV

"ENTER"

R5 = (Z █

"9", "ENTER"

R5 = (Z9 █

"1"

R5 = (Z9A $

"OR"

R5 = (Z9A + $

(NOT AR RL VL █N TM OC ZR NA NV

"ENTER"

R5 = (Z9A + Z █

"1" "0" "ENTER"

R5 = (Z9A + Z10 █

"1"

R5 = (Z9A + Z10A $

")"

R5 = (Z9A + Z10A) $

"AND" "NOT"

R5 = (Z9A + Z10A).^ $

(NOT AR RL VL █N TM OC ZR NA NV

""" """

(NOT AR RL VL ZN TM █C ZR NA NV

"ENTER"

R5 = (Z9A + Z10A) .^OC █

"4" "ENTER"

R5 = (Z9A + Z10a) .^ OC4 █

"ACK"

R█ = (Z9A + Z10A) .^ OC4

Equation Saved OK

Advertising