Document No: LT0122

F3200 Installation & Programming Manual

Installation & Wiring

Issue 2.7

5 July 2001

Page 8-15

8.5

WARNING SYSTEM WIRING

The typical configuration allocates the Ancil 3/Bells relay to drive the Warning System, and

has links Lk2-4 fitted so that a switched 24V output is available at the +/- terminals. The

supervision allows for up to 3 branches of wiring, with each requiring its own end of line

resistor (EOLR). The value of the EOLR varies with the number of branches such that the

combined total is always 3K3. The EOLR must be fitted at the end of each branch.

Branches

EOLR

1

3k3

2

6k8

3

10k

The Ancil 3/Bells output can be used to directly control alerting devices such as sounders

(that generate tones to AS2220), AVIs, strobes etc. If each device does not have an internal

series diode then a series diode must be fitted at each device. The diode must be rated to

carry the current of the device. Fig 8.5.1 shows a dual branch system with diodes fitted to

each device.

Note the Vigilant AVI requires an external series diode to be fitted at each device. Multiple

AVIs cannot presently be synchronised because the sync line carries the signal and is not

supervised (a revision of this is planned.) Refer to Fig 8.5.1. The AVIs should be used with

only two wires (+24V and EVAC-, or +24V and ALERT-), which is 3 Wire mode, but may

have to be used in 2-wire mode with the +ve lead connected to ALERT- (EVAC+) and the

–ve to EVAC- to get the required selection (e.g. Evac tone, top and bottom lamps both on).

The Bells +/- output is limited to 2A dc resistive max. (Note that loads such as AVIs, Mini-

Gens are considered resistive, whereas loads such as Solenoids and bells are inductive). A

load of up to 5A dc resistive can be accommodated by use of a Bell Monitor Board and a

separate, 6A dc, inline fuse. See Fig 8.5.6.

A relay on an 8 Relay Module can also be used to control and supervise a circuit of

evacuation devices. This is shown in Figure 8.5.3. Note that both poles of the relay are

needed and the relay needs to be programmed so that it doesn’t supervise the wiring when it

is activated (requires V2.09 or greater software). Although shown with only 1 circuit of

evacuation wiring, it can actually support two branches, using a 27k EOL resistor on each.

The Ancil 3/Bells relay can also be used to activate (and supervise) external tone generation

devices such as Mini-Gen, T-GEN, Microvac and QE90 this is covered in following sections.

MINI-GEN

The Vigilant Mini-Gen has an internal diode and can be connected with up to three branches

of speakers as per the instructions included with each unit. The 10k EOLR fitted to each

speaker line must be rated at 2W and is supplied with the unit. Refer Fig 8.5.2. If less than 3

branches are required, 10K 2W is still fitted to the end of each branch, with the other EOLRs

being fitted to the +/- dc input terminals of the furthest Mini-Gen. Refer to the instructions for

details.

The Mini-Gen can be link selected to produce an Alert tone, an Evac tone, an automatic

change from Alert to Evac after 1 minute, or an automatic change after 3 minutes. If desired,

it can be configured to produce Evac, with a relay switching the tone to Alert. For this, a mini-

jumper is fitted to link V, and the supplied 3 way connector fitted to link A/B with normally

closed relay contacts shorting pin 2 to 3 (position B) to produce Alert. When the contacts

open, the tone will change to Evac. Note that this applies only to Mini-Gen Rev 3 bds with

V2.00 or greater software, and for internal wiring of the relay to the Mini-Gen (i.e. the Mini-

Gen must be mounted within, or adjacent to the FIP.)