F3200 Installation & Programming Manual

Document No: LT0122

Installation & Wiring

Page 8-16

5 July 2001

Issue 2.7

T-GEN 50

The Vigilant T-GEN 50 is permanently powered, requiring a supervised Alarm- signal from

the FIP rather than switched power. The BELLS- terminal can be used for this unchanged.

Alternatively, an open collector output (if the T-GEN is in or adjacent to the F3200 panel),

another Ancil relay on the MAF, or an 8RM relay can be used as per Section 3.5 of the T-

GEN Installation Instructions, LT0186. Note that a 3k3 EOLR should be used for the BELLS

relay, and is also suitable for the other ANCIL and Module relays.

MICROVAC AND QE90

The Anc 3/Bells output can be used to activate a Microvac/QE90 and to supervise the link

for a fault condition. A 24V relay (e.g. PA0730 General Purpose Relay Bd) is required to be

mounted within the Microvac/QE90, and the wiring as shown in Fig 8.5.4.

Alternatively the Anc 3/Bells output can be made voltage-free (remove Lks 2, 3, 4 on the

MAF) and a spare 8 Zone Input can be used to supervise the Microvac/QE90. This

arrangement, shown in Fig 8.5.5, does away with the relay, but requires a 4-wire connection

and one spare input. The input should be programmed as a status-only zone and the fault

state included in the logic equation to generate a Warning System fault. E.g. for zone 16

WSF = Z16F.

A high level link can be achieved between the F3200 and QE90 using the RZDU

communications output. This is only suitable for when the F3200 and QE90 are co-located,

as there is no duplication of the cable. Details for this wiring are contained in the QE90

Installation and Commissioning Manual LT0088. In addition, the QE90 needs to be

supervised for a fault condition. This can be done as shown in Fig 8.5.5 using a spare zone

input or as in 8.5.4 using the Ancil 3/Bells output supervision.

┌───────────┬───────────┬──────────┐

│ ┌┴┐ ┌┴┐ │

│ │ │ │ │ │

│ ╘╤╛ ╘╤╛ │

│ │ │ │

│ ┌─┴─┐ ┌─┴─┐ ┌┴┐

│ │ │ │ │ │ │6k8

│ └─┬─┘ └─┬─┘ └┬┘

│ │ │ │

│ ┌─────┴───────────┴──────────┘

│ │

│ │

│ │

│ │

+ o

────────────┬───────────┴─────┼─────┬───────────┬──────────┐

┌┴┐ │ ┌┴┐ ┌┴┐ │

│ │DIODE │ │ │ │ │ │

╘╤╛ │ ╘╤╛ ╘╤╛ │

│ │ │ │ │

ANCIL 3

┌─┴─┐ │ ┌─┴─┐ ┌─┴─┐ ┌┴┐

BELLS

│ │ │ │ │ │ │ │ │6k8

└─┬─┘ │ └─┬─┘ └─┬─┘ └┬┘

│ │ │ │ │

- o

────────────┴─────────────────┴─────┴───────────┴──────────┘

FIG 8.5.1

EXAMPLE OF WIRING WITH 2 SUPERVISED BRANCHES

FOR DEVICES WITH NO INTERNAL SERIES DIODE