Document No: LT0122

F3200 Installation & Programming Manual

Applications

Issue 2.7

5 July 2001

Page 9-25

9.4.3.2

6 TERMINAL ISOLATED REPEATER

The following 6 terminal isolating repeaters can connect an F3200 zone to an IS detection
circuit using the circuit of Figure 9.4.3.2.

Pepperl & Fuchs

KHD3-ICR/Ex130 200

Pepperl & Fuchs

KFD2-CR-Ex1.30 200

OR

FIG 9.4.3.2

F3200 IS CIRCUIT USING 6-TERMINAL REPEATERS

Relay or Open Collector

For each AZC there must be either: a corresponding relay (e.g. Module Relay RLn) with

normally closed contacts breaking the supply to the Isolator as shown; or an open collector

output switching the supply 0V as shown. As the open collector is standard with an 8ZM it is

the cheapest alternative.