F3200 Installation & Programming Manual

Document No: LT0122

New Zealand Operation

Page 12-6

5 July 2001

Issue 2.7

PROGRAMMABLE OPTIONS (CONTINUED)

(d) Daily battery test

This is enabled by default. When enabled, every 24 hours (beginning at the auto test

start time) the charger voltage is reduced for 40 minutes and the battery voltage is

monitored.

Parameter Defaults for New Zealand Mode

The following is a list of the values set when New Zealand mode is enabled by a database

re-initialise or when New Zealand mode is manually enabled.

New Zealand Display Extender fitted

- as appropriate

Battery very low alarm

- disabled

Evac defect is fault

- enabled

External defect is fault

- enabled

Battery low monitor

- enabled

Battery connection test

- enabled

Hourly battery test

- disabled

Daily battery test

- enabled

Charger fault monitoring

- disabled

Mains fail = fault after 8 hours

- disabled

MCP

- disabled

Alarm buzzer

- enabled

Zone and system fault buzzer

- disabled

Daylight saving start and end time

- enabled

The daylight saving start time for New Zealand is set to 2am on the first Sunday in October

and the end time is set to 2am on the third Sunday in March.

12.5 LOGIC

TOKENS

The full list of logic tokens is given in Section 7.4.3.2. Logic tokens that are valid only in

New Zealand mode are:

NSA

local silence alarms (this does not include any received network bells silence

State – refer BLI).

TEV

Local trial evac operated.

BSR

Local services restore operated.

NEV

Evac defect input asserted.

NED

External defect input asserted.