F3200 Installation & Programming Manual

Network Programming

Issue 2.7

5 July 2001

Page 11-23

NDU OPERATION (CONTINUED)

Network setup

The parameters for Link TX time, Link RX time, groups etc should be programmed as for a

standard F3200.

Network SID configuration.

All 8 items that can be enabled per SID are relevant to an NDU and should be enabled or

disabled as necessary.

Network MAF config

The MAF status transmitted onto the network by an NDU may include alarm, isolate, fault,

brigade test, system fault, standby, and silence alarms.

Network command config

An NDU may send and receive commands on the network such as system tests, zone tests,

zone isolate/deisolate etc. All of the commands described in the F3200 Operator's Manual

apply to an NDU except that an NDU has no open collector outputs or module relays.

FFCIF config

This operates the same as F3200.

Network Event Config

An NDU may transmit events, event updates and text.

Network Variable Config

An NDU may send and receive output logic network variables.

Network Status Config

An NDU may have transmission of network status refresh data enabled, if desired, and this

will cause it to transmit the status of its local zones which include alarm zones 1-16, bells,

ancillary relays, and plant isolate zones.