F3200 Installation & Programming Manual

Document No: LT0122

Alignment, Adjustment & Placing into Operation

Page 10-2

5 July 2001

Issue 2.7

10.1

ALIGNMENT & ADJUSTMENT

All the F3200 modules (pcbs) are tested and aligned in the factory before being supplied to

the customer or fitted to a FIP. The only field adjustments that may be necessary are to set

the LCD contrast and the battery charger voltage.

Controller/Display

VR2

LCD Contrast

Adjust for best readability of the LCD when viewed from the

front of an installed FIP.

Factory adjustments include:

VR1

Set 1.2V Ref

Adjust for Charger High voltage of 28.1V to 28.15V.

VR3

Adjust 15.9V

Adjust until the 15.9V reference on TP15 is 15.90Vdc.

R94,

Fault Threshold

Snip as required to set Fault Threshold to

R105

nominal 19.03V.

MAF/PSU

PT1

Battery Charger Voltage

Should the battery charger voltage need adjusting, the method is as follows:

1.

Run the system with the door closed for at least 30 minutes to allow components to

"warm up" (the longer the better).

2.

Calculate the required no-load battery charging voltage by taking 27.3V for 20

°

C and

subtracting approximately 0.1V for every 3

°

C above 20

°

C, or adding approximately

0.1V for every 3

°

C below 20

°

C.

3.

With the system not in Alarm, disconnect the batteries.

4.

Measure the voltage at the battery terminals and adjust to the voltage calculated in

Step 2 by turning PT1.

5.

Re-connect the batteries.

PT2

+22V Supply is factory set and should not need field adjustment.