Module relay supervision – Tyco F3200 User Manual

Page 136

Advertising
background image

F3200 Installation & Programming Manual

Document No: LT0122

Programming System Configuration

Page 7-34

5 July 2001

Issue 2.7

7.5.3

MODULE RELAY SUPERVISION

This is option 2 of the Relay Supervision menu.

To program module relay supervision the desired relay number is selected by use of the

"NEXT" and "PREV" keys.

The options which may be selected are:

Supervision enabled (E) or disabled (D).

Supervision latching (L) or non-latching (N) (i.e. the fault condition).

Fault and isolate mapped (M) or not mapped to the MAF.

Supervision and relay status mapped to LED n on an LED Display (where fitted).

Isolatable (yes/no)

Testable (yes/no)

Supervise Activated State (yes/no)

The mode of monitoring is always "load" (refer to Sections 3.4.4 and 8.6).

The mapping of the relay status (activated, isolated, fault or normal) to LEDs on an LED

Display is described in Sections 2.3.2 and 7.3.3.