Module installation – Tyco F3200 User Manual

Page 143

Advertising
background image

Document No: LT0122

F3200 Installation & Programming Manual

Installation & Wiring

Issue 2.7

5 July 2001

Page 8-5

8.1.3 MODULE

INSTALLATION

The 8 Zone Modules and any 8 Relay Modules are fitted in order, from top to bottom. The

FRCs fit under each PCB, from BUS OUT of the top one to Bus IN of the next one (see Fig

8.1.2).

Observe the following:

(a)

When mounting to the cabinet the M3 mounting screw per module should be

tightened firmly to earth the module.

(b)

Modules and FRCs need to be fitted one at a time in the Cardframe. It is easier to

start from the bottom module and work up.

(c)

Care should be taken not to scrape an FRC against the bottom of the PCB above it.

(d)

There are redundant slots in the Cardframe to allow for either 6 module even spacing

or 8 module even spacing. Choose the correct slots.

(e)

On the Cardframe finger tighten the single M3 screw firmly into the notch in each

PCB as this earths the module.

FIG 8.1.2

MODULE CONNECTION WITHIN A CARDFRAME