Document No: LT0122

F3200 Installation & Programming Manual

Installation & Wiring

Issue 2.7

5 July 2001

Page 8-23

│ │ ─┬─

┌┴┐

│ │ │ │

└┬┘

┌─┴─┐ +┌─┴─┐ │

OCn

│ ├───────────────────────────────┤ ├───┴──────────────────────

└─┬─┘ └─┬─┘

│ Cct n


│ EOLR



┌─┴─┐ ┌─┴─┐

0V

│ ├───────────────────────────────┤ ├───── 0V

└─┬─┘ └─┬─┘

F3200

│ │OTHER EQUIPMENT

FIG 8.7.2

EXAMPLE OF INTERFACING TO OTHER EQUIPMENT, DIRECT COUPLING

┌───┐

+VBF

│ ├───────────────────────────┐ OPTOCOUPLER

└───┘ ┌┴┐ ┌───┐

RESISTOR

│ │ ┌─────┤ │+

E.G. 4K7

└┬┘ │ └───┘

│ / C Cct n

>

┌───┐ │ \ E ┌───┐

OCn

│ ├───────────────────────────┘ └─────┤ │-

└┬──┘ └─┬─┘

F3200

│ │OTHER EQUIPMENT

FIG 8.7.3

EXAMPLE OF INTERFACING TO OTHER EQUIPMENT, OPTICAL ISOLATION

8.8

ASE INSTALLATION AND WIRING

A Vigilant ASE may be mounted in an F3200 panel or an NDU in a large cabinet. Two kits

are available, namely KT0199 and KT0212. Both are 3U hinged front panels

accommodating 1 or 2 ASE or V-Modem units (or a combination) respectively. The kits

include mounting parts and fitting instructions.

The ASE should be wired directly off the battery via its own fuse. Wiring of the ASE FP0740

EOL unit is as per the ASE installation instructions. The red wires are wired across the MAF

Alarm relay NC and C terminals, the yellow wires across the MAF Fault relay NC and C

terminals, and the blue wires across the MAF Isolate relay NC and C terminals. No other

connections to these relays are permitted when the ASE EOL unit is used.

Locating the ASE remote from the panel has additional requirements under AS4428.1

(Clause 2.10) that currently cannot be met.