F3200 Installation & Programming Manual

Document No: LT0122

Applications

Page 9-24

5 July 2001

Issue 2.7

ISOLATED REPEATERS (CONTINUED)

DETECTOR

CAPACITANCE

INDUCTANCE

RESISTANCE

(FW ONLY)

C29BEx/Z94C

R24Bex

FW68

FW105
FW180

S231i+

S121

MS302Ex

MF301Ex

MR301Ex (Photo)

MR301TEX (HPO)

T56B (Heat)

(Z500N base)

T54B (Heat)

1Nf

3.3nF

84nF/km
66nF/km
57nF/km

1.5nF

4nF

1.5nF
1.5nF
1.5nF
1.5nF

0
0
0

1uH (0.001mH)

1.5mH

0.62mH/km
0.83mH/km
0.89mH/km

0
0
0
0
0
0
0
0
0

100Ω/km
100Ω/km
100Ω/km

TABLE 9.4.2

CAPACITANCE & INDUCTANCE PER I.S. DETECTOR

Notes

1.

The KHD0-ICS/Ex 251 or KFD0-CS-Ex 2.51P is effectively two KHD0-ICS/Ex 151 or

KFD0-CS-Ex 1.51P isolators (respectively) in one package.

2.

The resistance quoted in Table 9.4.2 for fire wire is per wire, thus the circuit

resistance of the pair is twice that amount.

3.

The FW68 and FW105 fire wires are not currently listed as IS.

4.

The MS302Ex, MF301Ex, MR301Ex, MR301TEx, S121 and S231i+ detectors are

currently not SSL approved.

For each of the following configuration options a table is included showing the limits of

detector quantity and cable length.