Tyco F3200 User Manual

Page 77

Advertising
background image

Document No: LT0122

F3200 Installation & Programming Manual

Programming

Issue 2.7

5 July 2001

Page 6-11

6.1.5

RECOMMENDED PROCEDURE FOR CONFIGURATION &
PROGRAMMING (CONTINUED)

10

Checking

When all parameters are entered, either:

1.

Print the database (as per Section 6.3.4) and compare the printout against

the configuration sheets (check each parameter for each item and tick off).

or

2.

If a printer is not available, de-access the database as per Section 6.3.3,

enter "View Parameter" mode and check each parameter of each item (tick

off) noting any mistakes. Re-access database and correct mistakes.

11.

Update RDU Programming

Update the programming (including zone names) of any connected RDUs. F3200

V2.03 (or later) software allows the sending of zone names to an RDU through the

RDU comms link. This is initiated with a command at the FIP and requires the RDU

to have its database link (Lk7) in the write enable position. RDU software V2.01 or

later supports this feature. Refer Section 6.2.1.

12.

Testing

As part of commissioning, with test loads rather than real ones (e.g. for

airconditioning shut-down and gas flood). Check the operation of detectors

(including LED brightness and remote LEDs). Check the operation of logic and

timers from inputs to outputs.

13.

Save Database

When satisfied that the configuration parameters and logic are correct, save the

database onto a disk (if a computer is available) and keep it in case the database

ever needs to be restored, or in case a future FIP has similar logic and could be

copied from this one and edited.

After saving the database a verify operation should be done as described in Section

6.3.7.

Advertising