Overview, General, Detector circuits – Tyco F3200 User Manual

Page 16: Displays, Overview -2, 1 overview

Advertising
background image

F3200 Installation & Programming Manual

Document No: LT0122

System Description

Page 2-2

5 July 2001

Issue 2.7

2.1 OVERVIEW

2.1.1 GENERAL

The F3200 is a self-contained, modular, intelligent Fire Indicator Panel (FIP) which performs

the functions of the Control and Indicating Equipment (CIE) as specified by the Australian

Standard AS1603.4 Automatic Fire Detection and Alarm Systems.

It is also available in formats that comply with AS4428.1. Refer to the relevant manuals that

apply to the AS4428.1 approved products.

The F3200 has a high degree of flexibility and expandability, catering for medium to very

large buildings from 8 zones or less, to 64 zones maximum. Refer to the constraints

specified in Section 3.1.3. More panels and zones can be added through the use of the

Vigilant Panel-link Network and the appropriate networkable F3200s.

This manual is also used for the installation of an NDU (Network Display Unit). NDU

operation is described in Section 11.11. An NDU may be programmed to operate in either

Australian mode (default) or New Zealand mode, and the operation of an NDU in New

Zealand mode is described in Chapter 12.

2.1.2 DETECTOR

CIRCUITS

The F3200 detector interface electronics caters for a wide range of detectors, including

various types which have high alarm current requirements. It also caters for interfacing to:

Intrinsically safe circuit barriers/isolators (hazardous areas).

Long line circuits e.g. from a sub-indicator FIP.

Tamper-proof circuits e.g. for water valve supervision.

A full range of compatible detectors is listed in the Appendix A.

2.1.3 DISPLAYS

The primary display of the F3200 is a 2 line by 40 character LCD on which status messages

and prompts are shown. The LCD has backlight illumination which is turned on when there

is an alarm or operator interaction.

Common conditions such as zone ALARM, ISOLATED and FAULT, and various system

states such as BELLS ISOLATED are displayed on LEDs adjacent to the LCD.

The display panel composed of the LCD, LEDs and operator keypad meets the requirements

of AS4050 (int) for a Fire Fighter's Control and Indicating Facility (FFCIF).

As an optional extra, individual zone status (ALARM, ISOLATE and FAULT) can be

displayed on LEDs by fitting the appropriate number of 16 Zone LED Display Bds.

The F3200 electronics includes, as standard, an open collector transistor output for each

zone which can be used to drive an internal or remote mimic display.