Led display installation, Zone labelling – Tyco F3200 User Manual

Page 144

Advertising
background image

F3200 Installation & Programming Manual

Document No: LT0122

Installation & Wiring

Page 8-6

5 July 2001

Issue 2.7

8.1.4

LED DISPLAY INSTALLATION

When LED Displays are required, the 7U inner door (ME0060) is fitted to the standard

cabinet directly below the 4U Operator Display with the M6 screws, washers and cage nuts

provided. The hinge is on the right hand side. Click the cage nuts in from the inside. (7U

doors cannot be fitted to a small cabinet).

The flat M6 washers have a sharp edge and a rounded edge. Fit washers to the screws with

the rounded edge facing the metalwork (to avoid damaging the paint).

The Display Bds mount to the inner door on the standoffs supplied. (FZ3031 for LH position,

FP0475 for others, both include the PCB, standoffs, FRC, power leads, diffuser and label

master).

Fit the FRCs and Minijump link as shown in Fig 8.1.3.

The LED Display power leads from the MAF/PSU must always be fitted.

8.1.5 ZONE

LABELLING

Zone labelling for the LED Displays can be done simply on a typewriter or word processor.

Note: For a typewriter use a photocopy of the label supplied with the Display Bd.

The type format is:

(a)

6 lines per inch.

(b)

20 characters at 10 CPI or 24 characters at 12 CPI.

(c)

2 lines per zone window.

(d)

1 line between each zone window.

To install the zone naming label:

(a)

Cut the typed label around the border, or cut the word processor sheet to 3mm to the

left of the text then 60mm wide and 220mm long.

(b)

Loosen the 4 Phillips-Head screws holding the display window.

(c)

Align zone text with windows.

(d)

Tape top and bottom of zone label.

(e)

Align clear, matt finish, light diffuser with the 3 columns of LED holes (next to the

label) with matt side in. Tape in place.

(f)

Tape blank sheets to unused zone window(s).

(g)

Replace display window and fasten the 4 screws.

Advertising