Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while
viewing System Setup Screen #2. The following screen will be displayed:

PAS (Positive Alarm Sequence) Delay

The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds
for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The following dis-
play will appear:

A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 005 for five seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will indi-
cate the new delay time.

Pre-signal Delay

The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of
001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen
#1. The following screen will be displayed:

SYSTEM SETUP

1=TIMERS

2=NAC

3=RELAYS

System Setup Screen #2

TIMERS

1=PAS DELAY 000

2=PRE SIGNAL 000

3=WATERFLOW 000

Timer Screen #1

TIMERS

1=AC LOSS DELAY 000

Timer Screen #2

TIMERS

1=PAS DELAY 000

2=PRE SIGNAL 000

3=WATERFLOW 000

Timer Screen #1

PAS DELAY

RANGE 0-180 SECONDS

PAS Delay Screen

PRESIGNAL DELAY

RANGE 0-180 SECONDS

Pre-signal Delay Screen