background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

49

Notification Appliance Circuits

Installation

2.4.2 Style Y (Class B) NAC Wiring

2.4.3 Style Z (Class A) NAC Wiring

Figure 2.7 NAC Style Y (Class B) Wiring

4 Style Y (Class B) Notification Appliance Circuits, supervised and power-limited - 4.7K ohm, ½ watt P/N:71252 UL-listed

Polarized Bells

Polarized Bells

Polarized Horns

Polarized Horns

Polarized Strobes

Notification Appliance Circuit
polarity shown in alarm state

Dummy Load all unused circuit

TB4

9600

na

cy.w

m

f

Polarized Strobes

circuit number

NAC 1

NAC 3

NAC 4

NAC 2

2 Style Z (Class A) Notification Appliance

Circuits, supervised and power-limited

Polarized Bell

Polarized Horn

Polarized Horn

Notification Appliance Circuit
polarity shown in alarm state

Polarized Bell

Polarized Strobe

Polarized Strobe

Figure 2.8 NAC Style Z (Class A) Wiring

96

00na

cz.cd

r

NAC 1

NAC 2