3 program check, Program check – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 141

Advertising
background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

141

Maintenance Programming Level

Programming

Pressing 2 while viewing the History Screen will cause the following screen to be displayed:

Pressing 1 while viewing the Erase History Screen will cause the message ERASING HISTORY,
PLEASE WAIT
to be displayed. The display will then return to the History Screen. Pressing 2 will
cause the display to return to the History Screen without erasing the History file.

3.7.3 Program Check

Pressing 3 while viewing Maintenance Screen #1 will cause the following screen to be displayed:

The Program Check feature allows the programmer to view the zones which have been pro-
grammed to the Notification Appliance Circuits on the control panel but have not been pro-
grammed to Initiating Devices as well as other circuits with no input or output correlations.
Pressing 1 while viewing Program Check screen will cause a screen similar to the following to be
displayed.

The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55, and 67 but
no input devices have been programmed to any of these zones. Use the up and down arrow keys to
view all the NAC zones without input assignments for NAC1, NAC2, NAC3, and NAC4.

ERASE HISTORY

PROCEED ?

1=YES 2=NO

Erase History Screen

PROGRAMMING

1=POINT PROGRAM

2=HISTORY

3=PROGRAM CHECK

Maintenance Screen #1

PROGRAM CHECK

1=NACS NO INPUT

2=ZONES NO INPUT

3=ZONES NO OUTPUT

Program Check Screen

NACS NO INPUT

NAC 1

25 31 44 55 67

NOTE: If the NACs have been configured for Class A in the Setup option, only NAC1 and NAC2 will
display test information. NAC3 and NAC4 will display asterisks (*) and will not be included in the test.

Advertising