MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

59

Optional Modules and Devices

Installation

installation details. Refer to “ANN-BUS Options” on page 121 for programming information.

Installation

Remote printers and PCs require separate primary power. Also required is the PRT/PK-CABLE
which is an interface cable prewired to a DB9F connector. Wire the PRT/PK-CABLE to TB7 Ter-
minals 1 - 4 as illustrated in the following figure. Connect the DB9F connector to the printer or PC
serial EIA-232 port. If a nine-pin serial connector is not available on the printer or PC, use a DB25
adapter. Make certain that the DB25 adapter does not swap the Transmit and Receive lines. Apply
power to the FACP and printer or PC. Note that a ground fault (zero impedance to ground) may
occur on the FACP, dependent on the printer or PC being used, due to this connection.
For this rea-
son, it is important that there be no preexisting ground fault on the panel.

Note that the printer may or may not be supervised as determined by user programming. Refer to
“Printer/PC” on page 134.

Printer Configuration

Refer to the documentation supplied with the printer for pertinent information about printer setup.
Set the printer’s options as listed in the following table:

PC Configuration

The Windows-based PK-CD Programming Utility Kit contains a CD-ROM with on-line help file.

2.6.6 Annunciators

Legacy ACM-8RF Relay Control Module

The ACM-8RF module provides eight Form-C relays with contacts rated for 5 amps.

!

CAUTION:

POSSIBLE EQUIPMENT DAMAGE

DO NOT CONNECT A PRINTER OR PC TO THE FACP IF A GROUND FAULT (ZERO IMPED-
ANCE TO GROUND) EXISTS ON THE CONTROL PANEL. CIRCUIT DAMAGE MAY RESULT.
REMOVE ALL POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY WIRING.

COMMUNICATION SETUP

BUFFER:

LARGE

DATA BITS:

7

PARITY:

EVEN

STOP BIT:

1 STOP

BAUD RATE:

2400/4800/9600

AUTOMATIC LINE FEED

NO

AUTOMATIC CARRIAGE RETURN

NO

RS-232 PC/PRINTER

B+ A+ B- A- B A

1 COMM 2

ACS

SHIELD

SLC

SLC

XMT RCV DTR GRND

T

B
7

T

B
6

T

B

8

RCV
DTR

GRND

TX

5 4 3 2 1

9 8 7 6

Figure 2.18 Serial Printer and Computer Connections

PRT/PK-CABLE

960

0

tb

7a

.w

m

f

Red

White

Green

Black