Read Status

4.22.1 System Point

Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be displayed:

The operator selects the loop containing the device to be read by pressing 1 for Loop 1 or 2 for
Loop 2. The following screen will then be displayed:

The operator now selects the type of device which is to be viewed by pressing 1 for Detector or 2
for Module. If 1 is pressed, the display will change to the following screen:

Entering the three digit detector address will cause the control panel to display the current status of
the selected device. For example, if a detector with address 001 on loop 1 is entered, a display sim-
ilar to the following will appear:

The information in the preceding display includes:

NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.)

SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could also be
ION for ionization smoke detector)

NORTH CLASSROOM - the Adjective/Noun label for this device

Z005 - the first of five possible assigned software zones

1D001 - 1 = Loop 1, D = Detector, 001 = Address 001

READ STATUS

1=SYSTEM POINT

2=ZONES

3=POWER

Read Status Screen #1

READ SYSTEM POINT

SELECT LOOP

1=LOOP 1

2=LOOP 2

READ SYSTEM POINT

SELECT TYPE

1=DETECTOR

2=MODULE

READ SYSTEM POINT

ENTER DETECTOR#

***

NORMAL SMOKE(PHOTO)

NORTH CLASSROOM

Z005

1D001