36

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Product Description

Accessories

ANN-LED Board Layout and Connection to FACP

Figure 1.13 illustrates the ANN-LED board showing locations of screw terminals for connection to
the FACP and the DIP switches for selecting the ANN-BUS ID number.

ANN-RLY Annunciator Module

The ANN-RLY relay module provides 10 programmable Form-C relays when used with a
compatible FACP.

Specifications

Operating Voltage: 24 VDC

Max. Current:

Alarm: 75 mA

Standby: 15 mA

Relay Contact Ratings

2 amps @ 30 VDC (resistive)

0.5 amps @ 30 VAC (resistive)

Operating Temperature: 32

o

F to 120

o

F (0

o

C to 49

o

C)

For indoor use in a dry location only

TB1

J1

SW
1

JP2

ANN-BUS

1 2 3 4 5 6 7 8

TB3

JP5

TB4

JP8

TB5

TB6

TB1

+ - + - + -

+ -

A B

Figure 1.13 ANN-LED Connection to FACP

FACP

ANN-LED

ANN-BUS/
ACS BUS

+24 VDC

-24 VDC

96

00

ls

tol

e

d.

w

m

f

ANN-BUS and power wiring are
supervised and power-limited

ANN-BUS (ID#)
Address DIP switch