Zone assignment z00 z** z** z** z – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 111

Advertising
background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

111

Master Programming Level

Programming

The programmer can select the notification appliance output by pressing the number corresponding
to the desired output. The coding selections are:

Steady - a continuous output with no coding

March Time - 120 ppm (pulse-per-minute) output

California - 10 seconds on and 5 seconds off

Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second off

Two Stage - refer to “Two Stage Operation” on page 111 for description

Selection of one of the above options will cause the control panel to store the information in mem-
ory and return the display to NAC Screen #2, which will display the new coding choice.

Two Stage Operation

Two Stage operation consists of the following:

1st stage output - 20 ppm (pulse-per-minute) coding

2nd stage output - Temporal coding as described above

If Two Stage operation is programmed as the Coding option, the following sequence of events will
occur during an alarm.

1. The on-board NACs which are programmed to General Alarm Zone 0 will activate with a 1st

stage output upon activation of any alarm point.

2. If the activated alarm point is directly mapped to a zone which is programmed to an on-board

NAC, that NAC will go directly to 2nd stage coding output. All other NACs not directly
mapped to the activated alarm point’s zone but assigned to Zone 0 will activate with a 1st stage
output.

3. If, after the programmed time of 3 or 5 minutes, the Acknowledge switch has not been pressed,

all NACs presently in 1st stage activation will go to 2nd stage activation.

4. If an Acknowledge switch has been pressed, any NACs currently in 1st stage activation will

remain in 1st stage. Pressing the Acknowledge switch does not affect NACs already in 2nd
stage activation.

5. If another alarm point is activated and the countdown timer is counting, the alarm point will

have no effect on the NACs unless the alarm point’s zones are directly mapped to one of the
NACs, in which case it will follow the procedure outlined in step 2.

6. If another alarm point is activated and the countdown timer has stopped counting due to the

Acknowledge switch being pressed, the countdown timer will restart and the NACs will
respond as outlined in step 2. NACs already in 2nd stage activation will not be affected.

7. Any control modules assigned to special Zone 99 will be activated either by direct mapping of

an input device programmed to Zone 99 or if the timer counts down to zero and the NAC goes
into 2nd stage coding.

8. Control modules that are programmed to the same zone as the activated input device will not

be delayed for activation.

Zone

A maximum of five zones can be programmed to each main circuit board NAC. Pressing 1 while
viewing NAC Screen #3 displays the following screen:

NAC #

1=ZONE

00 00 00 00 00

2=SIL INHIBITED NO

NAC Screen #3

ZONE ASSIGNMENT
Z00 Z** Z** Z** Z**

Zone Screen

Advertising