MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

113

Master Programming Level

Programming

To program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that
Relay 2 is fixed as a Trouble relay. Selecting Relay 2 will have no effect on its programming. The
following screen will appear for each relay to be programmed:

Pressing 1 for Type while viewing the Relay Screen will cause the following screens to be dis-
played:

While viewing the selected screen, press the number corresponding to the desired relay type to pro-
gram the main circuit board relay. The choice will be stored in memory and the display will return
to the Relay Type Screen which will show the programmed type choice. Press the Escape key to
return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.

Note the following:

1. AR (AutoResettable) in SUPERVISORY AR and PROCESS MON AR means that a relay with

the Supervisory and/or Process Monitor type code, when activated, will automatically reset
when the corresponding condition is cleared.

2. A relay programmed with the Silenceable Alarm type will activate upon any alarm and

deactivate when the FACP Alarm Silenced LED is illuminated.

Canadian Option

Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with Cana-
dian requirements. The display will change to Canadian Opt. On. Each press of the 1 key will
cause the display to toggle between Canadian Opt. On and Canadian Opt. Off.:

Important! For Canadian Applications, this option must be set to ON prior to any other panel pro-
gramming.

RELAY #

1=TYPE

ALARM

Relay Type Screen

RELAY

1=ALARM

2=SUPERVISORY

3=SUPERVISORY AR

Relay Screen #1

RELAY

1=TROUBLE

2=COMM FAIL

3=PROCESS MON

Relay Screen #3

RELAY

1=PROCESS MON AR

2=AC LOSS

3=HAZARD

Relay Screen #2

RELAY

1=MEDICAL

2=SILENCEABLE ALARM

Relay Screen #4

SYSTEM SETUP

1=CANADIAN OPT. OFF

2=WATERFLOW SIL. NO

System Setup Screen #3

SYSTEM SETUP

1=CANADIAN OPT. OFF

2=WATERFLOW SIL. NO