Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 121

Advertising
background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

121

Master Programming Level

Programming

ANN-BUS Options

Pressing 3 for ANN-BUS Options, while viewing the Annunciators screen, will cause the following
screens to be displayed:.

A printer module, graphic annunciator module, LCD annunciator module, LED annunciator mod-
ule and relay module can be programmed into the system. These devices communicate with the
FACP over the ANN-BUS terminals on the control panel.

ANN-BUS Enabled

The ANN-BUS must be enabled if any modules are connected to the ANN-BUS terminals. To
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads
Enabled Yes. Each press of the 1 key will cause the display to toggle between Enabled Yes and
Enabled No.

Modules Installed

If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select ANN-
BUS addresses for the module(s). The following screen will be displayed.

Pressing the down arrow key will allow the programmer to view additional screens displaying
Addresses 1-8. To program an ANN-BUS module to a specific address, press the number key cor-
responding to the desired address in each screen. The following screen will be displayed for each
address:

ANNUNCIATORS

1=TERM OPTIONS

2=ACS OPTIONS

3=ANN-BUS OPTIONS

Annunciator Screen

ANN-BUS

1=ENABLED NO

2=MODULES INSTALLED

3=AUTO-CONFIGURE

ANN-BUS Screen #1

ANN-BUS

1=ANN-S/PG OPTIONS

2=ANN-80 OPTIONS

ANN-BUS Screen #2

ANN-BUS MODULES

1=ADDR. 1 NONE

2=ADDR. 2 NONE

3=ADDR. 3 NONE

ANN-BUS Modules Screen #1

ANN-BUS MODULES

ANN-BUS ADDRESS #

1=TYPE NONE

ANN-BUS Address Screen