7 process monitor operation, 8 hazard condition operation – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 155

Advertising
background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

155

Process Monitor Operation

Operating Instructions

A typical Supervisory event would be displayed as illustrated in the following:

Note that, like alarms, supervisory signals latch (except when programmed for supervisory autore-
settable) and can be assigned to software zones. Supervisory alarms do not cause resound as do
other alarm conditions. Open circuits in supervisory wiring are processed by the control panel the
same way as other trouble conditions. Refer to “Alarm Operation” on page 153, for a description
of the information displayed on the control panel LCD.

4.7 Process Monitor Operation

Process Monitor operation will initiate the following events:

The piezo sounder pulses ¼ second On and ¼ second Off

The LCD displays a process monitor message along with the device name, type, address,
adjective/noun, associated zones and time/date

Relays programmed for process monitoring will be activated

The alarm relay is not activated

Silenced alarms are not resounded

Timers are not started

Store event in history buffer

Process Monitor condition must be Acknowledged before the FACP can be reset

Note that, like supervisories, process monitor signals latch (except when programmed for process
monitor autoresettable) and can be assigned to software zones.

4.8 Hazard Condition Operation

Hazard Condition operation will initiate the following events:

The piezo sounder turns on steady

The LCD displays a hazard message along with the device name, type, address,
adjective/noun, associated zones and time/date

Relays programmed for process monitoring will be activated

The alarm relay is not activated

Silenced alarms are not resounded

Timers are not started

Store event in history buffer

Hazard condition must be Acknowledged before the FACP can be reset

Hazard conditions latch and will therefore clear only when the hazard condition is cleared and the
panel reset. They can be assigned to software zones.

ACTIVE SUPERVISORY

<ADJ> <NOUN>

Z000

10:00A 010810 1M001