Programming

Master Programming Level

The following table contains control module type codes and their functions which are displayed in
the Control Type screens:

Silenceable

The Silenceable selection allows the programmer to select whether output devices connected to the
control module can be silenced, either by pressing the Alarm Silence key or by enabling Autosi-
lence. Pressing the 3 key while viewing Edit Control Screen #2 will enable the Silenceable feature
causing the display to read Silenceable Yes. Repeated presses of the 3 key will cause the display to
toggle between Silenceable Yes and Silenceable No.

Note that nonsilenceable outputs will not be activated for Fire Drill.

Walktest

The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable devices, which are connected to
a control module, for the Walktest feature, press 1 while viewing the Edit Control Screen #3 until
the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between
Walktest Yes and Walktest No. Refer to “Walktest” on page 160 for additional information.

Zone Assignment

A maximum of five zones can be programmed to each addressable control module. Pressing 2
while viewing Edit Control Screen #3 displays the following screen:

Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for
an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0
to the left. Enter the two digit number corresponding to the zone that is to be assigned to this
device. The cursor moves to the next Z** designation. Continue entering zone assignments or the

Control Type

Special Function

Bell Circuit

NAC Type - supervised

Horn Circuit

NAC Type - supervised

Sounders

NAC Type - supervised

Relay

Ignore Open Circuit

Strobe Circuit

NAC Type - supervised

Control

NAC Type - supervised

Resettable Power

1

1 When using a control relay module to supply resettable power to conventional 2-

wire smoke detectors, the MMF-302 monitor module must be set for smoke-
conventional operation.

Relay Type - Ignore Open Circuit

HVAC SHUTDN

2

2 For HVAC SHUTDN description, refer to “Control Module Operation” on

page 198.

Relay Type - Ignore Open Circuit

EDIT CONTROL

1=ENABLED

2=TYPE

3=SILENCEABLE

Edit Control Screen #2

EDIT CONTROL

1=WALKTEST

2=ZONE ASSIGNMENT

00 ** ** ** **

Edit Control Screen #3

ZONE ASSIGNMENT
Z00 Z** Z** Z** Z**

Zone Assignment Screen