MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Product Description

Circuits

Maintenance/presignal (yellow)

Alarm Silenced signals (yellow)

Disabled (yellow)

Battery fault (yellow)

Ground fault (yellow)

Key Panel

Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.

Function keys:

Acknowledge/Step

Alarm Silence

Drill

Reset (lamp test)

Service/program keys:

Keys labeled 1 to 9

* key

# key

0 (recall) key

1st Event key

Clear key

Escape key

Mode key

Four cursor keys (up, down, left and right)

Enter key

Local Piezo Sounder

A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory condi-
tions.

1.5 Circuits

SLC Communication Loop

One SLC loop is provided standard on the FACP main circuit board. A second SLC loop is avail-
able by plugging the optional SLC module into connector J3 on the main circuit board. SLC loops,
configurable for NFPA Style 4, 6 or 7, provide communication to addressable detectors, monitor
(initiating device) and control (output device) modules. Refer to the SLC Wiring Manual for infor-
mation on wiring devices.

Output Circuits

The following output circuits are available on the FACP:

Special Application Power
• 24 VDC Resettable (smoke detector power) output - 1.5 amps maximum
• 24 VDC Nonresettable power output #1 - 1.5 amps maximum
• 24 VDC Nonresettable power output #2 - 1.5 amps maximum

24 VDC Battery Charger (up to 26 AH batteries)

Figure 1.2 Membrane/Display Panel

960

0kyp

d.w

m

f