Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 126

Advertising
background image

126

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Programming

Master Programming Level

ANN-LED Options

Pressing 2 for Module Options while viewing ANN-BUS Address Screen when the ANN-LED
option is selected will display the following screen:

The first screen indicates that the ANN-LED at the selected ANN-BUS address is programmed to
annunciate Alarms, Supervisories and Troubles for SLC Loop #1 addressable Detectors with
addresses 1 through 10. The programming can be changed using ANN-LED Address Screens 2
and 3.

Pressing 1 while viewing ANN-LED Address Screen #2 will program the annunciator module to
annunciate either Point (addressable device address) information or Zone information.

Pressing 2 while viewing ANN-LED Address Screen #2 will program the annunciator module to
annunciate only Alarms for addressable device addresses 1-30 or Alarms, Supervisories and Trou-
bles for addressable device addresses 1-10.

Pressing 1 while viewing ANN-LED Address Screen #3 will select the Point or Zone range to be
annunciated (refer to the tables in “ANN-LED Zone Option - Alarm Only (for use with ANN-
RLED module)” on page 127
and “ANN-LED Point Option - Alarm Only (for use with ANN-
RLED module)” on page 129
).

Pressing 2 while viewing ANN-LED Address Screen #3 will select either addressable detectors or
addressable modules to be annunciated.

Pressing 3 while viewing ANN-LED Address Screen #3 will select the SLC loop with the address-
able devices to be annunciated.

ANN-LED ADDR #

LOOP1 DET 1-10

ALARM,SUPERV,TBL

ANN-LED Address Screen #1

ANN-LED ADDR #

1=POINT/ZONE

2=ALARM/ATS

ANN-LED Address Screen #2

ANN-LED ADDR #

1=RANGE

2=DET/MOD

3=LOOP#

ANN-LED Address Screen #3