2.6.2 4XTMF Transmitter Module Installation

The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition
to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open
with a system trouble condition if no alarm condition exists. A disable switch allows disabling of
the transmitter output during testing to prevent accidental calling of the monitoring service.

Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building

Figure 2.14 Wiring Phone Jacks

Green Wire

Red Wire

Green Wire

Red Wire

Tip

Ring

Ring

Tip

Ring

Tip

Tip

Ring

To premises phones

To premises phones

Secondary Lines

Incoming Telco

Phone Lines

Primary Lines

Incoming Telco Phone

Lines

Note: Shorting bars inside RJ31X Jack
removed during male plug insertion

Primary Phone Line PRI

Secondary Phone Line SEC

Male Plug

Connectors

Female

Connectors

7 foot cable

(MCBL-7)

order separately

DACT-UD2

CAUTION: It is critical that the

DACT-UD2 be located as the first

device on the incoming telephone

circuit to properly function

96