Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 68

Advertising
background image

68

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Programming

Master Programming Level

A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit detector address, such as 005.

When the last digit is keyed-in, the following screen will be displayed:

Press the down arrow key to view additional choices. Press the number corresponding to the
desired selection to program that type to the newly added detector.

When the type has been selected, the following screen will be displayed:

The programmer can continue adding detectors by pressing the ESC or left arrow key which will
return the display to the Add Detector Screen.

Delete Detector

Pressing 2 in the Detector Screen will display the Delete Detector Screen which allows the pro-
grammer to delete a specific detector:

A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit detector address, such as 005. When the last digit is keyed-in, the following screen
will be displayed:

The programmer can continue deleting detectors by pressing the ESC or left arrow key which will
return the display to the Delete Detector Screen.

DETECTOR TYPE

1=SMOKE(PHOTO)

2=USER-DEFINED-1

3=SMOKE(ION)

ADD DETECTOR

DETECTOR# 005

IS ADDED

DETECTOR

1=ADD

2=DELETE

3=EDIT

Detector Screen

DELETE DETECTOR

ENTER DETECTOR#

***

Delete Detector Screen

DELETE DETECTOR

DETECTOR# 005

IS DELETED

Advertising