MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

191

NFPA Standard-Specific Requirements

NFPA 72 Remote Station Protective Signaling System

Notes:

1. Cut Jumper JP6 on the FACP main circuit board to supervise placement of the 4XTMF

module.

2. Refer to “4XTMF Transmitter Module Installation” on page 55 for detailed information.

RS82 Remote Station Receiver UL listed.
Refer to Fire•Lite Alarms, Inc., Instruction Manual for Remote
Station Receiver Model RS82.

+ -

Polarity Shown is
Normal Standby

4XTMF Transmitter Module

Cutting TBL Jumper allows the
reverse polarity circuit to open with
a system trouble condition if no
alarm condition exists.

Power-limited

Figure C.4 Remote Station Connection Using 4XTMF Module

+

-

(Dummy load with a 4.7K

, ¼ watt resistor

when no connection is made)