Table c.2 411-ud connections to facp – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 189

Advertising
background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

189

NFPA Standard-Specific Requirements

The following figure illustrates an example of Central Station/Remote Station Reporting using a
411UD. The relay contacts from the FACP may be used to trip any dialer UL listed for Central
Station/Remote Station Reporting Services.

Figure C.2 FACP Connection to 411UD

Note: The Monitor Module input, which is being used to monitor
the 411UD Relay #2 Output (programmed for DACT Trouble),
must be programmed as ‘Trouble’ at FACP.

Channel1

Channel 2

Channel 3

Channel 4 (2.2K ELR)

Relay Output (DACT Trouble)

Monitor Module ELR resistor

FACP
Supervisory Relay

FACP
Alarm Relay

(2.2K ELRs
P/N 27070)

J4 Not Installed

411UD

Monitor Module Circuit Input

SLC Loop

+ -

FACP

960

04

11

u.w

m

f

24 VDC
nonresettable
power

1 2 3 4 5 6

1

2

3

4

5

6

7

8
1

2

3

4

5

6

7

8

9

1 2 3

Monitor Module*

FACP
Trouble Relay

*If the SLC device does
not match the one in this
figure, refer to the SLC
manual appendix, which
contains wiring conversion
charts for type V and type
H modules.

411UD

FACP

Alarm

TB2-1

TB1-1

TB2-2

TB1-3

Trouble

TB2-3

TB5-2

TB2-4

TB5-3

Supervisory

TB2-5

TB5-4

TB2-6

TB5-6

Table C.2 411-UD Connections to FACP