Operating Instructions

Read Status

4.22.3 Power

Pressing 3 while viewing Read Status Screen #1 will display the following screens:

A real-time display of control panel voltages can be used to determine if system problems exist.
Note that Zones Screen #3 will only be displayed if the NACKEY NAC option card is installed, in
JP8 of the main circuit board, for Class B operation.

The following table lists the circuit being measured, possible conditions and their respective volt-
age ranges:

Circuit

Condition

Voltage Range

Battery

Normal Battery (nominal)

27.05 to 28.15 VDC

Low Battery

20.0 to 20.8 VDC

No Battery

0 to 18.36 VDC

24V Resettable

Normal

21.25 to 27.50 VDC

24V Nonresettable

Normal

21.25 to 27.50 VDC

Charger

Normal

27.05 to 28.15 VDC

NACs

Normal

-1.3 to -1.6 VDC

Open Circuit

-2.3 to -2.5 VDC

Short Circuit

0 to 1.0 VDC

POWER

BATTERY 27.21V

24 V RST 25.31V

Zones Screen #1

POWER

CHARGER 28.36V

NAC 1 -2.39V

NAC 2 -2.39V

Zones Screen #2

POWER

NAC 3 -2.39V

NAC 4 -2.39V

Zones Screen #3