Appendix b: default programming – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 186

Advertising
background image

186

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Appendix B: Default Programming

The following table provides a list of the programming options and their factory default settings.

Program Option

Factory Default

Program Option

Factory Default

Master Password

00000

NAC Enable

Enabled

Maintenance Password

11111

NAC Silenceable

Yes

Detector Programming

Not Installed

NAC Type

Bell

Detector Type

Smoke-Photo

NAC Sync Type

System Sensor

Detector Verification

Off

NAC Autosilence

0

Detector Walktest

Yes

NAC Coding

Steady

Detector PAS

No

NAC Zones

Zone 000 only

Detector Presignal

No

NAC Silence Inhibit

0

Detector Zone Assign.

000 only

Relay 1

Alarm

Detector Adj/Noun

none

Relay 2

Trouble

Module Programming

Not Installed

Relay 3

Supervisory

Module Type

Monitor

On Board DACT

No

Module Walktest

Yes

Annunciator Terminal Mode

No

(not used)

Annunciator ACS Mode

No

Module Presignal

No

UDACT

No

Module Zone Assign.

000 only

ACS Installed

No

Module Adj/Noun

none

Printer-PC

No

Zone 0 Enable

Enabled

Printer Baud

9600

Zone 1 Enable

Enabled

Canadian Option

Off

Zone 2 Enable

Enabled

Waterflow Silenceable

No

Zone 3 Enable

Enabled

ANN-BUS Enabled

No

.........................through..........

.....................

Central Station Reporting

Disabled

Zone 99 Enable

Enabled

AC Loss Delay

2 Hours

Special Zones 97, 98 & 99

Disabled

DACT Backup Reporting

First Available

Zones 0 - 99 Type

Monitor

DACT Report Style

By Point

Loop 1 & 2 Style

Style 4

ANN Enabled

No

Loop 1 & 2 Protocol

LiteSpeed

ANN-BUS Modules Addr. 1 - 8

None

Trouble Reminder

Off

ANN-S/PG Port

Parallel

Banner

ANN-S/PG Baud

9600

Time Format

12 Hr

ANN-S/PG Data Bits

7

Hours Setting

12

ANN-S/PG Parity

Even

Minutes Setting

00

ANN-S/PG Stop Bits

1

Second Settings

00

ANN-S/PG Offline Timer

60

AM-PM Setting

AM

ANN-S/PG Printer Supervision

No

Month Setting

01

ANN-80 Piezo Enabled

Yes

Day Setting

01

ANN-80 Lock Enabled

Yes

Year Setting

00

ANN-80 Acknowledge Button Enabled

Yes

PK-Plus Secret Code

00000000

ANN-80 Silence Button Enabled

Yes

Trouble Call Limit

0

ANN-80 Reset Button Enabled

Yes

Daylight Savings

Yes

ANN-80 Drill Button Enabled

Yes

Month Start Daylight Savings

March

ANN-I/O Point/Zone

Zone

Week Start Daylight Savings

2nd Week

ANN-I/O Range

00-29

Month End Daylight Savings

November

ANN-I/O Active LEDs Only

Week End Daylight

1st Week

ANN-RLY Relay 1

Zone 1

Verification

No

................through.......................

............

Ring Count

0

ANN-RLY Relay 10

Zone 10

PAS Timer

0

ANN-LED Point/Zone

Zone

Presignal Timer

0

ANN-LED Alarms/ATS (Alarm, Trbl, Supv)

ATS

Waterflow Retard Timer

0

ANN-LED Range

0 - 9