Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 175

Advertising
background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

175

Calculating the System Current Draw

Power Supply Calculations

‘Secondary’ refers to the control panel’s backup batteries

All currents are given in amperes (A). Table 5.2 shows how to convert milliamperes and
microamperes to full amperes.

5.3.2 How to Use Table 5.3 on page 176 to Calculate System

Current Draw

Use Table 5.3 on page 176 to calculate current draws as follows:

1. Enter the quantity of devices in all three columns.
2. Enter the current draw where required. Refer to the Device Compatibility Document for

compatible devices and their current draw.

3. Calculate the current draws for each in all columns.
4. Sum the total current for each column.
5. Copy the totals from Column 2 and Column 3 to Table 5.4 on page 177.

Following are the types of current that can be entered into Table 5.3 on page 176:

Calculation Column 1 - The primary supply current load that the control panel must
support during a non-fire alarm condition, with AC power applied.

Calculation Column 2 - The primary supply current load that the control panel must
support during a fire alarm condition, with AC power applied.

Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm
condition during a loss of AC power.

To convert...

Multiply

Example

Milliamperes (mA) to
amperes (A)

mA x 0.001

3 mA x 0.001 = 0.003A

Microamperes (µA) to
amperes (A)

µA x 0.000001

300 µA x 0.000001 = 0.0003 A

Table 5.2 Converting to Full Amperes

Advertising