MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

17

Controls and Indicators

Product Description

1.3.1 Current Availability

The following figure illustrates the maximum current that is possible for each panel circuit and the
total current available from the FACP power supply.

1.4 Controls and Indicators

LCD Display

The FACP uses an 80-character (4 lines X 20
characters) high viewing angle LCD display.
The display includes a long life LED backlight
that remains illuminated. If AC power is lost and
the system is not in alarm, the LED backlight will
turn off to conserve batteries.

LED Indicators

LED indicators are provided to annunciate the following conditions:

AC Power (green)

Fire Alarm (red)

Supervisory (yellow)

Trouble (yellow)

1

2

3

4

5

6

7

8

1

2

3

4

5

6

TB4

TB3

Figure 1.1 Current Availability

p

owe

rd

ist96

00

ls2

.w

mf

*The combined output current of all Special Applications Power circuits cannot exceed 1.5 amps in standby. Each
circuit is capable of delivering the full 1.5 amps individually.

Refer to the battery calculations section for additional information.

1.5 amps max

per circuit

1.5 amps max

per circuit

1.5 amps max

per circuit

3 amps max

per circuit

3 amps max

per circuit

3 amps max

per circuit

3 amps max

per circuit

Standby

1.5 Amps Max*

per panel

Resettable Special
Application Power
for 4-wire smoke detectors

Alarm

7 Amps Max

per panel

Resettable Special
Application Power
Power #1

Resettable Special
Application Power
Power #2

NAC 1

Style Y or Z

NAC 2

Style Y or Z

NAC 3

Style Y only

NAC 4

Style Y only