Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 172

Advertising
background image

172

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Operating Instructions

Read Status

Drift Compensation

Drift compensation uses software algorithms that identify and compensate for long-term changes in
the data readings from each addressable smoke detector. These long-term changes in detector data
readings are typically caused by dirt and dust accumulation inside the smoke chamber. Drift com-
pensation performs the following functions:

Samples each photoelectric smoke detector every 6 seconds and each ionization smoke
detector every 3 seconds

Allows a smoke detector to retain its original ability to detect actual smoke and resist false
alarms, even as dirt and dust accumulate

Reduces maintenance requirements by allowing the control panel to automatically perform the
periodic sensitivity measurements required by NFPA Standard 72

The FACP software also provides filters to remove transient noise signals, usually caused by elec-
trical interference.

Maintenance Alert

The software determines when the drift compensation for a detector reaches an unacceptable level
that can compromise detector performance. When a detector reaches an unacceptable level, the
control panel indicates a maintenance alert. Table 4.1 summarizes the three levels of maintenance
alert:

Figure 4.1 illustrates a graphic representation of the maintenance levels:

Maintenance Level

FACP Status Displays Indicates

Low Chamber Value

INVREP

A hardware problem in the detector

Maintenance Alert

DIRTY1

Dust accumulation that is near but below the allowed
limit. DIRTY 1 indicates the need for maintenance
before the performance of the detector is compromised

Maintenance Urgent

DIRTY2

Dust accumulation above the allowed limit.

Table 4.1 Maintenance Alert Levels

Figure 4.1 Diagram of Maintenance Levels

DIRTY

Acceptable

Range

Maintenance
Urgent

Maintenance
Alert

Low Chamber
Reading

LOW

VALUE

Advertising