Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 25

Advertising
background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

25

Accessories

Product Description

The total worst case current is calculated as follows:

Using this value and referring to the Wiring Distance Table 1.1 on page 24, it can be found that the
available options are:

463 feet maximum using 22 Gauge wire

1,172 feet maximum using 18 Gauge wire

1,866 feet maximum using 16 Gauge wire

2,953 feet maximum using 14 Gauge wire

Wiring Configuration

Figure 1.3 illustrates the wiring between the FACP and ANN-BUS devices.

ANN-80 Current Draw

= 3 X 0.040 amps

= 0.120 amps

ANN-S/PG Current Draw

= 1 X.0.040 amps

= 0.040 amps

ANN-I/O Current Draw

= 1 X.0.200 amps

= 0.200 amps

Total Worst Case Current Draw

= 0.360 amp

TB1

B A (+) (-)

4 3 2 1

TB3

JP5

TB4

JP8

TB5

TB6

TB1

+ - + - + -

A B

+ -

Figure 1.3 FACP wiring to ANN-BUS Device

ANN-BUS Device

FACP

ANN-BUS and power wiring are

supervised and power-limited

24 VDC
nonresettable

ANN-BUS/

ACS BUS

96

00

lst

o

an

n8

0.w

m

f

Advertising