11 phone line, 12 central station, Phone line 4.22.12: central station – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 169

Advertising
background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

169

Read Status

Operating Instructions

4.22.11 Phone Line

Pressing 2 while viewing Read Status Screen #4 will display the following screen:

The second and third lines of this screen indicate that both the Primary and Secondary phone lines
have been configured for touchtone dialing operation.

Pressing 3 while viewing the Phone Line screen will cause the following screen to be displayed:

This screen indicates whether or not Phone Line 2 is being supervised. In this example, PHONE
LINE 2 NO indicates the phone line is not being supervised.

4.22.12 Central Station

Pressing 3 while viewing Read Status Screen #4 will display the following screens:

Central Station Screen #1 indicates whether the Central Station Reporting is enabled or disabled, if
the Reports will be sent to the First Available or Backup Primary and Secondary Central Station
phone numbers and Call Limit for DACT trouble calls within a 24 hour period. Central Station
Screen #2 provides information on the Report Style (Zone or Point) as well as the Primary and Sec-
ondary Central Station programming which includes:

Test Time Interval

Account Code

24 Hour Test Time

Phone Number

Communication Format

Event Codes

PHONE LINE

PRIMARY TOUCHTONE

SECONDARY TOUCHTONE

3=SUPERV PHONE LINE

SUPERVISE PHONE LINE

PHONE LINE 2 NO

READ STATUS

1=ANNUNCIATORS

2=PHONE LINE

3=CENTRAL STATION

Read Status Screen #4

CENTRAL STATION

REPORTING ENABLED

REPORT FIRST AVAIL

CALL LIMIT 10

Central Station Screen #1

CENTRAL STATION

1=PRIMARY

2=SECONDARY

REPORT STYLE ZONE

Central Station Screen #2