Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 83

Advertising
background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

83

Master Programming Level

Programming

Monitor module type selection will affect the function of the point as follows:

Monitor Type

Action When Activated

Pull-Station

Fire Alarm

User-Defined-1

same as previous (Pull-Station)

Waterflow

Fire Alarm Delayed

User-Defined-2

same as previous (Waterflow)

Monitor

Fire Alarm

User-Defined-3

same as previous (Monitor)

Future

not used

Future

not used

Smoke-Conventional

1

1 Conventional 2-wire smoke detectors may be powered using an external power supply

with an SLC Control Relay Module programmed for Resettable Power operation (refer
to note 1 on page page 89).

Fire Alarm

User-Defined-5

same as previous (Smoke-Conventional)

Heat-Conventional

Fire Alarm

User-Defined-6

same as previous (Heat-Detector)

Medic-Alert

2

2 Combination systems employing these non-fire monitor types require the SLC loop to

be programmed by the installer for Style 4 operation and isolator modules must be
employed on each non-fire branch of the SLC as per Figure 13 in the Fire-Lite SLC
Wiring Manual (document number 51309). Fire and non-fire devices must not be used
on the same SLC branch.

Supervisory, latching

User-Defined-7

same as previous (Medic-Alert)

Hazard-Alert

2

Supervisory, latching

User-Defined-8

same as previous (Hazard-Alert)

Tornado-Alert

2

Supervisory, latching

User-Defined-9

same as previous (Tornado-Alert)

Phone

Active Phone (LCD display only)

User-Defined-10

same as previous (Phone)

Tamper

Supervisory, nonlatching (tracking)

User-Defined-11

same as previous (Tamper)

Supervisory

Supervisory, latching

User-Defined-12

same as previous (Supervisory)

Supervisory-AR

3

3 For all entries ending in AR, AR refers to AutoResettable.

Supervisory, nonlatching (tracking)

User-Defined-13

same as previous (Supervisory-AR)

HVAC OVRRIDE

4

4 For HVAC RESTART and HVAC OVRRIDE descriptions, refer to “Monitor Module

Operation” on page 198.

Switch Supervisory, nonlatching (tracking)

Power-Monitor

Power Fault

User-Defined-14

same as previous (Power Monitor)

Trouble-Monitor

Trouble

User-Defined-15

same as previous (Trouble Monitor)

Process-Monitor

2

Piezo

User-Defined 16

same as previous (Process-Monitor)

Process-Monitor-AR

2, 3

Piezo, nonlatching (tracking)

User-Defined-17

same as previous (Process-Monitor-AR)

Future

not used

Future

not used

Ack-Switch

Acts like panel Acknowledge Key

Sil-Switch

Acts like panel Silence Key

Reset-Switch

Acts like panel Reset Key

Drill-Switch

Acts like panel Drill Key

PAS-Bypass

PAS Disable

HVAC RESTART

4

Switch

Drill-Switch-AR

3

Drill Switch, nonlatching (tracking)

Table 3.1 Monitor Types