Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 110

Advertising
background image

110

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Programming

Master Programming Level

Auto Silence

The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable
notification appliances after a programmed length of time. To enable this feature and program the
time delay before Auto Silence activation, press 1 while viewing NAC Screen #2. The following
screens will be displayed:

To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. When a time delay is selected, the information will be stored
in memory and the display will return to NAC Screen #2.

Coding

The Coding feature allows the programmer to select the type of output that the main circuit board
notification appliances will generate when activated. Pressing 2 while viewing NAC Screen #2
will cause the following displays to appear:

NAC #

1=AUTO SILENCE

2=CODING

TEMPORAL

NAC Screen #2

AUTO SILENCE

1=NO

2=5 MINUTES

3=10 MINUTES

Auto Silence Screen #1

AUTO SILENCE

1=30 MINUTES

Auto Silence Screen #2

AUTO SILENCE

1=15 MINUTES

2=20 MINUTES

3=25 MINUTES

Auto Silence Screen #3

CODING

1=STEADY

2=MARCH TIME

3=CALIFORNIA

Coding Screen #1

CODING

1=TEMPORAL

2=TWO STAGE 3 MIN

3=TWO STAGE 5 MIN

Coding Screen #2