Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 69

Advertising
background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

69

Master Programming Level

Programming

Edit Detector

The programmer can change a detectors existing or factory default programming by pressing 3 in
the Detector Screen. The following screen will be displayed:

A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit detector address, such as 017.

When the last digit is keyed-in, if the selected address has not been added to programming, a screen
showing information about a device that is installed with a lower address, closest to the selected
address, will be displayed.

If no detectors have been installed on the loop, the following will be displayed:

If the selected address has been added to programming, device summary screens will be displayed.
These screens allow the programmer to view all device settings at a single glance. Pressing the left
or right arrow keys will allow the programmer to rapidly view the devices at the previous or next
address (if installed).

If a detector (such as a photoelectric detector) with the selected address is not physically installed
on the SLC or has a communication fault but the address is programmed in the system, the follow-
ing screen will be displayed:

EDIT DETECTOR

ENTER POINT ADDRESS

***

Edit Detector Screen

NO DETECTOR

INSTALLED

Edit Detector Screen #1

TROUBL SMOKE(PHOTO)

********************

ZNNN

* 1D017

Edit Detector Screen #1