Nac (notification appliance circuit), Ac loss delay range 00-23 – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 107

Advertising
background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

107

Master Programming Level

Programming

Pressing 2 while viewing AC Loss Delay Screen #1 will display the following screen:

A flashing cursor will appear in the lower left corner of the display. The factory default setting is
02 hours. Type the two digit AC loss reporting delay in hours (00 to 23 hour delay). When the sec-
ond digit is entered, the display will return to AC Loss Delay Screen #1.

NAC (Notification Appliance Circuit)

The options for the NACs on the control panel main circuit board can be set by pressing 2 while
viewing System Setup Screen #2. The following screens will be displayed:

The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2
for NAC 2, 3 for NAC 3, or 4 for NAC 4.

Note that 3=NAC 3 and 4=NAC 4 will only be displayed if the NACKEY NAC option card is
installed, in JP8 of the main circuit board, for Class B operation.

AC LOSS DELAY

RANGE 00-23

AC Loss Delay Screen #2

SYSTEM SETUP

1=TIMERS

2=NAC

3=RELAYS

System Setup Screen #2

NACS

1=NAC 1 3=NAC 3

2=NAC 2 4=NAC 4

NAC Selection Screen