Zones installed, Zones enabled, Zones installed zones enabled – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 146

Advertising
background image

146

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Programming

Maintenance Programming Level

nected to the control module can be used to indicate a PAS condition in the control panel. Do not
assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condi-
tion.

Pressing 2 will cause the display to change to Pre-signal 98 On. Each press of the 2 key will cause
the display to toggle between Pre-signal 98 On and Pre-signal 98 Off. When Zone 98 is pro-
grammed On, a Pre-signal activation of any device will cause Zone 98 to activate. By assigning
Zone 98 to a control module in the Programming Zone Assignment Screen, an output device con-
nected to the control module can be used to indicate a Pre-signal condition in the control panel. Do
not assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal
condition.

Zone 99, in special purpose mode, is reserved for future use and has no effect.

Zones Installed

Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will display a screen similar to
the following:

This display will show all of the zones that have been programmed into the control panel. Note that
an up and/or down arrow may appear in the upper right corner of the display, indicating that addi-
tional screens of zone information exists. Press the up or down arrow keys to view the additional
zones.

Zones Enabled

Pressing 2 for Zones Enabled, while viewing Zone Setup Screen #2, will display a screen similar to
the following:

This display will show all of the zones that are enabled in the control panel. Note that an up and/or
down arrow may appear in the upper right corner of the display, indicating that additional screens
of zone information exists. Press the up or down arrow keys to view the additional zones.

ZONE SETUP

1=ZONES INSTALLED

2=ZONES ENABLED

3=ZONES DISABLED

Zone Setup Screen #2

ZONES INSTALLED

00 01 02 03 04 05

Zones Installed Screen

ZONES ENABLED

00 01 02 04 05 06 07

08 09 10 11 12 13 14

15 16 17 18 19 20 21

Zones Enabled Screen