Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 14

Advertising
background image

14

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Product Description

Features and Options

Optional module for adding a second SLC loop which meets NFPA Style 4, 6 and 7
requirements

318 addressable device capacity for each SLC loop (159 detectors and 159 control/monitor
modules)

99 software zones

Up to four onboard NACs (Notification Appliance Circuits):
four Style Y (Class B) or two Style Z (Class A)

Additional NAC capability using control modules

7.0 amps total power for NACs and 24 VDC auxiliary power outputs in alarm

Two programmable relay outputs and one fixed trouble relay

EIA-232 Printer/PC interface (variable baud rate)

80-character LCD display (backlit)

Real-time clock/calendar with daylight savings time control

History file with 1,000 event capacity

Advanced fire technology features:
• Automatic drift compensation
• Maintenance alert
• Detector sensitivity test capability (NFPA 72 compliant)
• Automatic device type-code verification
• Point trouble identification

Waterflow selection per module point

Alarm verification selection per detector point

Walktest, silent or audible

PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)

New ANN-BUS Annunciators/Modules (ACS annunciators cannot be used when ANN-BUS
annunciators/modules are connected)
• ANN-80 Remote Liquid Crystal Display point annunciator
• ANN-I/O LED Driver Module
• ANN-LED Alarm, Trouble, Supervisory Annunciator (minimum of one required for

Canadian applications)

• ANN-RLED Alarm Annunciator
• ANN-S/PG Serial/Parallel Printer Module
• ANN-RLY Form-C Relay Module
• Automated activation of the ACC-25/50(ZS/T) Audio-Command-Center

Legacy ACS/Term Annunciators: (ANN-BUS annunciator/modules cannot be used when
ACS/Term annunciators are connected)
• ACM Series-LED Zone Annunciators
• LDM Graphic Annunciator Series
• LCD-80F Liquid Crystal Display point annunciator (LCD-80FC for Canadian applications)
• ACM-8RF Relay Module

Silence inhibit timer option per NAC

Autosilence timer option per NAC

Continuous, March Time, Temporal or California code for main circuit board NACs with two-
stage capability

Selectable strobe synchronization per NAC

Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules, legacy ACS
annunciators or ANN-80 Remote annunciator