Installation

Optional Modules and Devices

3. Carefully plug connector J3 on the SLC-2LS module into connector J3 on the

MS-9600LS/MS-9600UDLS main circuit board, being careful not to bend any pins

4. Secure the SLC-2LS Expander Module to the four standoffs installed in step 2 with the four

supplied screws (or the screws removed in step 2)

5. Connect the SLC wiring and devices to TB8 on the SLC Expander Module. Refer to the SLC

Wiring Manual for wiring information

6. Reapply power to the control panel
7. Program the addressable devices connected to the SLC-2LS Expander Module as detailed in

“Master Programming Level” on page 65

8. Test the system for proper operation

2.6.5 Printer/PC

A serial printer or a PC (personal computer) may be connected to TB7 Terminals 1 - 4 on the FACP.
The printer can be used to provide a hard-copy printout of real-time events, history file and walktest
data. An IBM compatible PC can be connected to provide local FACP programming capabilities
using the PS-Tools programming utility. Installation of either device requires panel programming
to allow the FACP to communicate with the device.

A parallel printer may also be connected to the FACP using the optional ANN-S/PG Serial/Parallel

Interface Module. Refer to “ANN-S/PG Serial/Parallel Interface Installation” on page 30 for

Figure 2.17 SLC-2LS Expander Module Installation

SLC-2LS Expander Module

FACP

SLC Loop 2

Shield B
Shield A

SLC A-
SLC B-

SLC A+
SLC B+

SLC Loop 1

Shield B
Shield A

SLC A-
SLC B-

SLC A+
SLC B+

96

op

tslc.wmf

Remove four screws and replace

with four supplied metal standoffs